APPLICATION
CWT BW493 may be applied either continuously or intermittently to the boiler system. For dealkalizer regenerate additive, BW493 should be included with each charge of the
regeneration chemical. Actual dosages, methods of application and frequency to be determined by field study of problem by your field representative.
PHYSICAL PROPERTIES
Color and Form........................................... Amber Viscous Liquid
Specific Gravity............................................ 1.520 to 1.540
pH.............................................................. Greater than 14.0
Density....................................................... 12.7 to 12.8 lbs./gal.
Odor........................................................... Musty
Dosage & Feeding
For continuous boiler applications CWT BW493 can be fed directly from chemical drum by suitable mechanical feeding equipment. AWT BW493 may also be added to chemical
mix tank with other boiler water chemicals and fed proportionally to the boiler feedwater. CWT BW493 may be fed directly into the boiler to adjust the boiler water
alkalinity when using CWT BW493 as a supplemental to dealkalizer regenerate, apply directly into the brine tank in appropriate amounts.
Handling & Precautions
CWT BW493 is a strong caustic and corrosive material. Do not take internally. Avoid contact with skin. Avoid breathing vapors. If skin and eyes are affected, flush
with plenty of fresh water and obtain medical attention. If swallowed, do NOT induce vomiting. In preparation of solutions for feeding, fill dilution vessel with water
and add AWT BW493 to the water. Some heat may be evolved. Avoid use of copper or aluminum alloys in handling or feeding equipment.
Packaging
Cannon Water Technology's BW493 is packaged in :
5- Gallon Pails.......................................... Net Weight 60 pounds
55 - Gallon Drums....................................... Net Weight 650 pounds
|