CWT BW103 will maintain boilers clean and efficient.
APPLICATION
BW103 is intended for use in boilers operating in the low and medium pressure range. For best results, use this product in boiler systems having softened or low hardness feed
water.
PHYSICAL PROPERTIES
Form…………………………………….. Liquid
Color.......................................................... Light Amber
pH.............................................................. 12.0 +/-
Density....................................................... 9.82#/gallon.
Odor........................................................... Slight Ammonia
Dosage & Feeding
Normal use range is from 1.0 to 2 pints per 1000 gallons of make up water. Chemical control range is 20 – 40 ppm Sulfite as (SO3).
CWT BW103 should be fed proportional to feed water or system makeup flow. For best results, feed this product to the feed water storage tank or feed water line using a
chemical metering pump. CWT BW103 may be mixed in solution with other supplemental boiler treatments. Dilution water should be low hardness and below 100 degrees
Fahrenheit.
Handling & Precautions
Do not take internally. Do not use in potable water systems. Avoid prolonged contact with skin. If skin and eyes are affected, flush with plenty of fresh water
and obtain medical attention. Keep container closed when not in use.
Packaging
Cannon Water Technology Inc.'s BW103 is packaged in :
5 - Gallon Pails........................................... Net Weight 49 pounds
15 – Gallon Drums………………………. Net Weight 147 pounds
30 - Gallon Drums....................................... Net Weight 294 pounds