Loop-powered blind analog transmitter

  • Two-wire 4-20 mA output
  • Exact digital setting of the 20 mA flow rate
  • Rugged cast aluminum housing with fused coating
  • Electronic components potted solid in urethane for maximum moisture protection
  • Can be meter or wall mounted
  • Test switch to force 4 and 20 mA outputs
  • Variable averaging to smooth output from particularly turbulent flows

Download: Manual

ao55large
ao55feat

Spectifications:

Power

12-36 VDC

Temperature

32° to 130°F (0° to 55°C)

Input

open-collector solid-state

Minimum Freqency

10 Hz (@20 mA)

Maximum Frequency

999.9 Hz

Output

proportional 4-20 mA

Frequency Settings

4 rotary DIP switches

Input Averaging

2 to 16 seconds (switch selectable)

Response Time

2 to 60 seconds
90% of full scale
(dependant on input averaging)

ao55spec01

FAQ's

Q.

How do I span the 4-20 mA signal?

A.

The 20 mA set point is entered as a frequency, using four  rotary switches. A simple calculation determines the frequency. The unit is  microcontroller-based, and it digitally adjusts itself when the 20 mA frequency  is entered.

Q.

How do I power the flow sensor?

A.

The flow sensor gets its power from the AO55, which gets its  power from the 4-20 mA signal itself. Both the flow sensor and the AO55  transmitter can operate on the 4 mA minimum current.

Q.

What does "loop powered" mean? What does "two-wire 4-20  mA mean?"

A.

They basically mean the same thing. See the answer above.