Model 350 pH Cooling Tower Controller
Product Information

The Model 350 allows you to control acid and/or caustic feed in order to maintain desired pH levels in your
cooling tower. This model features an alarm timer which prevents excessive chemical feed and a flowswitch
which prevents chemical feed if there is no sample flow. For cooling tower applications only. Includes plumbing.
Specifications
|
Inputs
|
|
|
Power
|
120 VAC 120/240 VAC w/-WP
|
|
Sensor
|
pH Combination glass electrode in PVC housing
|
|
Flow switch
|
Dry contact
|
|
Outputs
|
|
|
Relays
|
3 Amps @ 120 VAC
|
|
0-1 mA
|
non isolated
|
|
4-20 mA
|
isolated, internal power w/-35
|
|
Plumbing
|
|
|
Pressure
|
140 psi (9.7 bar) 100°F (38°C)
|
|
Max. Temperature
|
140°F (60°C)
|
|
Min. Flow
|
1 gpm (3.8 Lpm)
|
|
Controller
|
|
|
pH Range
|
5-10 pH
|
|
Accuracy
|
±0.05 pH
|
|
Resolution
|
0.01 pH
|
|
Deadband
|
Adjustable
|
|
Setpoints
|
HIGH and LOW
|
|
Alarm Timer 5-90 minutes.
|
Locks out both HIGH and LOW setpoints.
|
|
Ambient Temperature
|
32-158°F (0-70°C)
|
|
Electrical Rating
|
UL Listed
|
|
Enclosure
|
ABS Plastic
|
|
|
NEMA 4X Optional
|
Ordering Information
|
350
|
|
pH controller for acid and caustic feed that has dual setpoints, 5-10 pH scale, a feed limit
timer with push button reset, flowswitch, sensor, power cord, outlets and a digital display. UL Listed.
|
|
|
|
CONTROLLER OPTIONS (optional)
|
|
-CRPH
|
|
Custom setpoint dial; 0-14 pH
|
|
|
|
REMOTE SENSOR OPTIONS (optional)
|
|
-RPFS
|
|
Unlimited distance. Preamp, sensor, flowswitch and sensor tee. Cable must be provided by customer
|
|
|
|
ENCLOSURE OPTIONS (optional)
|
|
-WP
|
|
Watertight enclosure with 120/240VAC 50/60 Hz power switch. ½ inch conduit knockouts. No outlets or power cord.
|
|
|
|
PLUG-IN OUTPUT OPTIONS (optional, select one only)
|
|
-35
|
|
Isolated 4-20 mA output for remote data acquisition.
|
|
-39F
|
|
Frequency output contact for electronically pulsed chemical pump.
|
|
-39P
|
|
Percent on-time modulating contact for solenoid chemical feed systems.
|
|
-42
|
|
HIGH/LOW alarm contacts with adjustable setpoints.
|
|
-44
|
|
Isolated 4-20 mA output plus High and Low alarms.
|
|