2412 Conductivity Controller 
by Lakewood Instruments
Home  >> Products  >> Controllers  >> Lakewood  >> Tower  >> 2412  >>

 

Custom Search
1_800_230-1427

 

AWT Logo Sm1
dealer_logo1

Model 2412 Microprocessor-Based pH & Conductivity Cooling Tower Controllers

Product Information

LONWORKS® Technology is the latest in microprocessor capability that gives the user the highest level of application flexibility. A large graphic screen, multiple inputs and very easy setup with easy field upgrade characterize this new technology.

* LONWORKS is a registered trademark of Echelon Corporation.

Benefits

  • Multiple control options in a single economical package.
  • Very accurate control of chemical feed and cycles of concentration.
  • Very low maintenance.
  • Tolerant to power surges and brownouts.
  • Power cord, plug outlets and attached plumbing make installation easy. There is plenty of protected room inside the enclosure for electrician wiring.
  • Very accurate monitoring of the evaporated water.
  • Feeds chemical AFTER blowdown.
  • Has expansion slots to add additional control, such as chiller loop monitor and cycles of concentration based on incoming makeup water.

Features

  • 4-electrode conductivity includes fouling compensation and alarm.
  • Differential pH sensor with diagnostics indicate fouled reference or broken glass.
  • Integral flowsight & flowswitch lockout.
  • Records both makeup (MTR1) and blowdown (MTR2) water meter total gallons.
  • Configure blowdown water meter (MTR2) as second makeup meter.
  • Blowdown Relay options:
  • Bleed x gallons for every x gallons makeup
    Bleed x minutes for every x gallons of makeup
    Bleed by setpoint
    Bleed by cycles of concentration with NCON/NCKT
    Option
    Bleed by multi-setpoint selected with
    NCON/NCKT Option
  • Three user-selectable relay options (four additional with NRLY):
  • Feed by setpoint, direct or reverse;
    Water meter actuated feed. MTR1, MTR2 or sum;
    Feed after blowdown by percent of bleed time;
    Feed by percentage of time;
    Schedule feed timer (-RTC Option);
    General alarm contact.
  • Three security levels:
  • View only
    Operator
    Technician
  • Four different languages.
  • English Spanish (standard)
    English French (optional)
    English German (optional)

Specifications

 

Inputs

 

Power

80-300 VAC

Sensor

4 electrode Conductivity pH glass electrode and reference electrode

Temperature comp.

Automatic

Flow switch

Dry contact

Water Meter Input

Two contacting head or open collector

Outputs

 

Relays

Four, 3 Amps @ 120 VAC

4-20 mA

Two, isolated w/-35L

Sensor/Plumbing

 

Pressure

140 psi (9.7 bar) @ 100°F (38° C)

Max. Temperature

140°F (60° C)

Min. Flow

1 gpm (3.8 Lpm)

Controller

 

Conductivity Range

0-5,000 m S (other ranges optional)

Conductivity Accuracy

±40 µS

Conductivity Resolution

10 µS

pH Range

0-14 pH

pH Accuracy

±0.05 pH

pH Resolution

0.01 pH

Deadband

Adjustable

Setpoints

Direct or Reverse (configurable in the field)

Feed timer

Adjustable

Keypad

Numeric

Display Illumin.

128x64 pixel LCD

Ambient Temperature

32-158° F (0-70° C)

Enclosure Rating

ABS Plastic

 

NEMA 4X Optional

Ordering Information

2412

 

LONWORKS Technology-based pH and conductivity controller with plumbing and flow switches. Four relays are integral to the system. One is dedicated to blowdown. The others may be configured for pH (acid or caustic), inhibitor feed on conductivity, water meter, percent of time or schedule feed. pH range is 0-14 and conductivity range is 0-5,000 µS.

 

CONTROLLER OPTIONS (optional, select no more than three)

-RTC

 

Adds 24-hour clock and calendar to controller (required to configure relays to feed chemicals/biocides based on time of day and for data acquisition if using the -RS2L Option). NOTE: Adding an -RTC card does not add relays.

-35L

 

Two 4-20 mA outputs configurable for remote data acquisition of conductivity and pH.

-RS2L

 

Communications node with shareware software. Requires -RTC Option.

-NIN

 

Network interface node. Allows 1 NRLY and/or up to 3 NCON/ NCKT's to be added.

 

ENCLOSURE OPTIONS (optional)

-WP

 

Weatherproof and watertight. ½ inch knockouts. No outlets or power cords.

 

LANGUAGE OPTIONS (optional, choose one, English and Spanish Standard)

-EF

 

English and French.

-EG

 

English and German.

 

REMOTE NODE OPTIONS (optional, MUST purchase -NIN Option above)

NRLY

 

Four additional relays with enclosure (1 per 2000 Series Controller).

NCON

 

Conductivity node for makeup water or closed loop control (node only).

NCKT

 

Conductivity node for makeup water or closed loop control with PVC sensor, tee and enclosure. Maximum water pressure and temperature is 100°F (38°C) @ 140 psi (9.7 bar).

 

SOFTWARE AND EXTERNAL MODEMS

LRWS

 

Windows-based registered software for computer to communicate with 2000 Series Controllers.

MD4X

 

High Baud modem in NEMA 4X enclosure ready to power.

MD

 

High Baud modem for use with 2000 Series Controllers.

 